Isishwankathelo
Iimveliso zethu ezintsha, i-NVS1-24 i-series ye-indoor high-voltage vacuum vacuum breakers isetyenziselwa ukuguqula i-switchgears kwi-24kV inkqubo yamandla, njengeyunithi yokulawula kunye nokukhusela izixhobo zombane kumashishini oshishino kunye nemigodi, izityalo zamandla kunye neendawo ezincinci. Ngenxa yeenzuzo ezikhethekileyo ze-vacuum circuit breaker, ifanelekile ngokukodwa kwimisebenzi eyenziwa rhoqo efuna ukulinganisa ukusebenza ngoku, okanye iindawo apho i-short-circuit current yaphuka amaxesha amaninzi. I-breaker circuit ithatha uyilo oludibeneyo lwendlela yokusebenza kunye nomzimba we-circuit breaker. Ezi zimbini ziyisakhiwo sangaphambili nasemva, esinomsebenzi othembekileyo wokudibanisa. I-breaker circuit ingasetyenziselwa njengeyunithi yokufakela esisigxina. Isenokuxhotyiswa ngelori ye-chassis kwiyunithi yenqwelo yesandla.
Imigangatho yemveliso
I-GB/T1984-2014 I-voltage ephezulu ye-AC Circuit Breaker
I-JB/T3855-2008 3.6-40.5kV yangaphakathi AC Isixhobo esinamandla sombane esinamandla
DL/T403-2000 12kV-40.5kV ombane ophezulu ombane uvacuum umaphuli wesekethe ukuodola iimeko zobugcisa
I-IEC62271-100: 2008 Isixhobo sokutshintsha amandla ombane aphezulu kunye nesixhobo sokulawula iSigaba 100: Izaphuli zesekethe ze-AC
Iimeko zokusingqongileyo
Ubushushu be-Ambient: -15 C ~+40C
O Ukufuma kwe-Ambient: Umndilili wemihla ngemihla wokufuma okuzalanayo
Uxinzelelo lomphunga lwemihla ngemihla
O Ukuphakama ≤ 1000m;
O Ubunzulu benyikima
O Indawo yofakelo: Indawo kufuneka ingabi namanzi, ingozi yogqabhuko-dubulo, ungcoliseko olukhulu, umhlwa weekhemikhali kunye nokushukuma okugqibeleleyo.
IiParameters eziphambili zobuGcisa
Into | Iyunithi | Idatha |
Umbane olinganisiweyo | kV | amashumi amabini anesine |
Ilinganiswe rhoqo | Hz | 50 |
Ilinganiswe ngemizuzu eyi-1 yokumelana nombane (isigaba ukuya kwisigaba, emhlabeni, ukwaphuka) | kV | 65 |
Isantya sombane esilinganiselweyo sokumelana nombane (isigaba ukuya kwisigaba, emhlabeni, ukwaphuka) | kV | 125 |
Ulandelelwano lomsebenzi olukalisiweyo |
| Ot-INTONI-t'-YINTONI |
Into | Iyunithi | I-NVS1-24 | ||||||||||
Ikalwe ngoku | A | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | 1250 | 1600 | 2000 | 2500 | 3150 |
Ilinganiswe kwisekethe emfutshane yokwaphulwa kwangoku | kA | 20/25 | 31.5 | 40 | ||||||||
Ilinganiswe kwisekethe emfutshane yokwenza yangoku (incopho) | kA | 50/63 | 80 | 100 | ||||||||
Ubungakanani bexesha lesekethe emfutshane | s | 4 | 4 | 4 | ||||||||
Ilinganiswe ngamaxesha oqhawulo lwesekethe emfutshane | ixesha | 50 | 50 | 30 | ||||||||
Ubomi bomatshini | ixesha | 20000 | 20000 | 20000 |
Phawula:
20/25/31.5kA, t=0.3s t'=180s
40/50kA, t=180s, t'=180s
I-4000A VCB idinga ukupholisa umoya ngenkani
Into | Iyunithi | Idatha | ||||
Usulelo phakathi kwabafowunelwa abavulekileyo | mm | 13±1 | ||||
Ukuhamba ngaphezulu | 3.5±0.5 | |||||
Izigaba ezintathu zokuvula kunye nokuvala i-asynchronism | Nksk | ≤2 | ||||
Ixesha lokuvala unxibelelwano lokuvala | Nksk | ≤ 3 (50kA) | ||||
Uxinzelelo loqhagamshelwano lokuvala abafowunelwa | N | 20kA | 25 kA | 31.5 kA | 40 kA | 50 kA |
2000±200 | 2400±200 | 3100±200 | 4250±250 | 5500±300 | ||
Isantya sokuvula esiphakathi | Nksk | 1.1~1.6 | ||||
Isantya sokuvala esiphakathi | 0.6~1.0 |
Umzobo weSakhiwo ngokubanzi kunye nobungakanani boFakelo (iyunithi: mm)