NVS1-12 Series Indoor High Voltage Vacuum Circuit Breaker

Inkcazelo emfutshane:


Iinkcukacha zeMveliso

Iithegi zeMveliso

Isishwankathelo

Iimveliso zethu ezintsha, i-NVS1-12 ichungechunge lwangaphakathi lwe-high-voltage vacuum circuit breakers lusetyenziselwa ii-switchgears kwi-12kV inkqubo yamandla, njengeyunithi yokulawula kunye nokukhusela izixhobo zombane kumashishini oshishino kunye nemigodi, izityalo zamandla kunye neendawo ezincinci. Ngenxa yeenzuzo ezikhethekileyo ze-vacuum circuit breaker, ifanelekile ngokukodwa kwimisebenzi eyenziwa rhoqo efuna ukulinganisa ukusebenza ngoku, okanye iindawo apho i-short-circuit current yaphuka amaxesha amaninzi. I-breaker circuit ithatha uyilo oludibeneyo lwendlela yokusebenza kunye nomzimba we-circuit breaker. Ezi zimbini ziyisakhiwo sangaphambili nasemva, esinomsebenzi othembekileyo wokudibanisa. I-breaker circuit ingasetyenziselwa njengeyunithi yokufakela esisigxina. Isenokuxhotyiswa ngelori ye-chassis kwiyunithi yenqwelo yesandla.

 

Imigangatho yemveliso

I-GB/T1984-2014 I-voltage ephezulu ye-AC Circuit Breaker

I-JB/T3855-2008 3.6-40.5kV yangaphakathi AC Isixhobo esinamandla sombane esinamandla

DL/T403-2000 12kV-40.5kV ombane ophezulu ombane uvacuum umaphuli wesekethe ukuodola iimeko zobugcisa

I-IEC62271-100: 2008 Isixhobo sokutshintsha amandla ombane aphezulu kunye nesixhobo sokulawula iSigaba 100: Izaphuli zesekethe ze-AC

 

Iimeko zokusingqongileyo

Ubushushu be-Ambient: -15 C ~+40C

O Ukufuma kwe-Ambient: Umndilili wemihla ngemihla wokufuma okuzalanayo

Umyinge woxinzelelo lwemihla ngemihla lomphunga

O Ukuphakama ≤ 1000m;

O Ubunzulu benyikima

O Indawo yofakelo: Indawo kufuneka ingabinangozi yokuphuma kwamanzi, ungcoliseko olumandla, ukonakala kweekhemikhali kunye nokushukuma okugqibeleleyo.

 

IiParameters eziphambili zobuGcisa

Into Iyunithi Idatha
Umbane olinganisiweyo kV 12
Ilinganiswe rhoqo Hz 50
Ilinganiswe ngemizuzu eyi-1 yokumelana nombane (isigaba ukuya kwisigaba, emhlabeni, ukwaphuka) kV 42
Isantya sombane esilinganiselweyo sokumelana nombane (isigaba ukuya kwisigaba, emhlabeni, ukwaphuka) kV 75
Ulandelelwano lomsebenzi olukalisiweyo   Ot-INTONI-t'-YINTONI

 

Into Iyunithi

I-NVS1-12

Ikalwe ngoku A 630 1250 1250 1600 2000 2500 1250 1600 2000 2500 3150 3150 4000
Ilinganiswe kwisekethe emfutshane yokwaphulwa kwangoku kA 20/25 31.5 40 50
Ilinganiswe kwisekethe emfutshane yokwenza yangoku (incopho) kA 50/63 80 100 125
Ubungakanani bexesha lesekethe emfutshane s 4 4 4 4
Ilinganiswe ngamaxesha oqhawulo lwesekethe emfutshane ixesha 50 50 30 20
Ubomi bomatshini ixesha 20000 20000 20000 10000

 

Phawula:

20/25/31.5kA, t=0.3s t'=180s

40/50kA, t=180s, t'=180s

I-4000A VCB idinga ukupholisa umoya ngenkani

 

Into Iyunithi Idatha
Usulelo phakathi kwabafowunelwa abavulekileyo mm 9±1
Ukuhamba ngaphezulu 3.5±0.5
Izigaba ezintathu zokuvula kunye nokuvala i-asynchronism Nksk ≤2
Ixesha lokuvala unxibelelwano lokuvala Nksk ≤2 (50kA)
Uxinzelelo loqhagamshelwano lokuvala abafowunelwa N 20kA 25 kA 31.5 kA 40 kA 50 kA
2000±200 2400±200 3100±200 4250±250 5500±300
Isantya sokuvula esiphakathi Nksk 0.9~1.3
Isantya sokuvala esiphakathi 0.4~0.8

 

Umzobo weSakhiwo ngokubanzi kunye nobungakanani boFakelo (iyunithi: mm)

 

1NVS1 dimension1 1NVS1 dimension2 1NVS1 dimension3

NVS1 dimension4

 


  • Ngaphambili:
  • Okulandelayo: