I-VBI-12 enye indlela yokusebenza yasentwasahlobo yimveliso edibeneyo eyenzelwe ngokukodwa inqanaba lesithathu i-AC 50Hz, i-voltage elinganisiweyo ye-12KV yangaphakathi ye-voltage ye-vacuum ye-circuit breaker operation. Iyimodyuli yoyilo lweyunithi esebenzayo kunye nesakhiwo esincinci kwaye esilula. Ithembekile kwaye kulula ukuyisebenzisa. Uyilo olulungisiweyo lweyunithi yokuvala umsebenzi lunciphisa amandla okuvala, angasombululi kuphela ngokusisiseko ukwenzeka kokusilela okufana nokusilela ukugcina kunye nokwala ukuvula emva kokuvalwa, kodwa kwakhona kunciphisa amandla ohambo afunekayo ekuvuleni; iyunithi yokugcina amandla emoto Yamkela ukuhanjiswa kwegiya kunye nesakhiwo esixineneyo, esinciphisa ukusilela koomatshini ngenxa yeengxaki ezisemgangathweni ezinje ngamatyathanga. Ngaloo ndlela, kuphuculwe kakhulu ukuba iyunithi yokugcina amandla emoto enqanyuliweyo yamkele ukuhanjiswa kwegiya, inesakhiwo esibambeneyo, kwaye inciphisa ukusilela koomatshini okubangelwa ziingxaki zomgangatho ezinje ngamatyathanga. Ngaloo ndlela iphucula kakhulu ubomi bomatshini bendlela yentwasahlobo ye-circuit breaker (amaxesha angama-30,000). Umphezulu we-80% yamacandelo omatshini uphathwa ngenkqubo ekhethekileyo, ephucula kakhulu amandla okuthintela ukubola kwamacandelo kwaye iqinisekisa umgangatho ohambelanayo kunye nozinzile womatshini.

Iimeko zokusingqongileyo

1.Ubushushu be-Ambient: -15℃~+40 ℃ (e--30 ℃ ukuvumela ukugcinwa kunye nokuthutha).
2. Ukuphakama: ≤1000m.
3. Ukufuma okuhambelanayo: umyinge wemihla ngemihla ≤95%, umyinge wenyanga ≤90%. Uxinzelelo lomphunga ogcweleyo imihla ngemihla≤2.2kPa, umndilili wenyanga ≤1.8 kPa.
4. Ubunzulu benyikima: ≤8 degree.
5. Akukho mlilo, ingozi yogqabhuko-dubulo, ukungcola okumasikizi, ukuthotywa kweekhemikhali, kunye neendawo zokungcangcazela okukhulu.

 

1. Indlela yokusebenza yesaphuli sesekethe esinemagnethi esisigxina yesigaba esinye sokugcina amandla emoto yeDC, amandla okugcina ngokulandela idata yobugcisa:

Uhlobo Ulinganiso lweVoltage(V) Amandla (W) Uluhlu oluqhelekileyo lokusebenza (V) Amaxesha ogcino lwamandla ombane olinganisiweyo (S)
ZY55-1 DC 110
DC 220
70(80) 85%~110% ≤ 10

* Umbane osebenzayo usebenzisa amandla e-AC/DC. ( ) nge 40kA ipharamitha.

2. Idatha yezobuchwepheshe yekhoyili yendlela yokusebenza kunye nokukhululwa

Igama Amandla (W) Ulinganiso lwamandla ombane osebenzayo (V) Uluhlu lwamandla ombane osebenzayo Amagqabantshintshi
Ikhoyili yokuvala 368 DC220
DC110
I-85% -110% yombane olinganisiweyo
Ikhoyili yokuvula 368 65% -120% amandla ombane <30% amandla ombane akufuneki avuleke
Vimba ikhoyili 4.8 DC110 I-85% -110% yombane olinganisiweyo
Ukukhutshwa kwangoku i-Y7 (Y8,Y9) - Yangoku 5A-3.5A